CXV/DATA – AXV/DATA 3.6/6 (7.2)kV

Power cable, three-cores, copper or aluminium conductor, armoured (double of aluminium tape), sheathed

Standards: IEC 60502-2, TCVN 5935

Cable identification: with color tapes lie between insulation screen and metallic screen

  • Cores: Red, yellow, blue
  • Outer sheath: Black

The above identifying can be changed as order

Characteristics:

  • Rated voltage Uo/U(Um): 3,6/6(7,2)kV
  • Max. conductor temperature in normal use: 90oC
  • Min. bend radius: 12 x D (D: overall diameter of cable)

Construction: Cu(Al)/XLPE/PVC/DATA/PVC

  1. Conductor: Annealed plain copper or aluminium (class 2, compacted circular)
  2. Conductor screen: Semi-conductive compound
  3. Insulation:  Cross-linked Polyethylene (XLPE)
  4. Insulation screen: Semi-conductive compound
  5. Metallic screen: Copper tape
  6. Filler, binder: PP, PET
  7. Separation sheath: PVC
  8. Metallic armour: Double of aluminium tape (DATA)
  9. Outer sheath: PVC (type ST2)